| Brand | ReoTemp |
| Series | TSTDS |
| Output Signal | 4-20mA, 3-wire (standard), 0-5V, 0-10V, 1-6V (3-wire), Switchable from 4-20mA to 0-10 VDC |
| Measuring Principle | Thin-film-on-steel |
| Pressure Ranges | Vacuum, Compound, Pressure to 7,500psi |
| Accuracy NLH at 77 ° F (BSL) | ±0.25% of span, ±1.0% of span with 3/4" Tri-Clamp Input: 15-30 Vdc (4-20mA), 15-30 Vdc (0-5V, 1-6V), 15-30 Vdc (0-10V) |
| Temperature | Temperature effect with 1.5" or 2" Tri-Clamp®: ±0.1% of span/10 ° F (for zero and span) or ±0.02 psi/10 ° F (greater of). Note: 3/4" Tri-Clamp® not recommended for temperature variations. Effect is less than or equal too ±0.9 psi/10 ° F, Media: -13 to 185 ° F, Ambient: -13 to 185 ° F |
| Environmental Rating | IP67 |
| Switching Output | 2 Transistors PNP |
| Pressure Unit for Display | PSI, Bar, MPa, kPa, mWC, mmWC, %, User Scale |
| SKU | Please choose an option below |
| Manufacturer | Reotemp |
| Product Type | M12 x 1 Connection |
| Material | Stainless Steel |
| Size | 3 in. Tri-Clamp |
| Weight | 3.00 LBS |
Description The Reotemp TSTDS Sanitary Pressure Transmitter & Switch is engineered for precision and reliability in demanding sanitary applications, making it ideal for a variety of processing environments. Built with durable 316 stainless steel wetted parts, it withstands harsh cleaning and sterilization procedures while maintaining long-term stability. Its rotatable housing and display allow for flexible installation in tight or complex piping systems, ensuring optimal visibility and ease of use. With a wide selection of electrical outputs and user-configurable display units, the TSTDS adapts seamlessly to a range of process control requirements. Designed to perform in extreme process conditions, it supports 3-A Tri-Clamp® sanitary connections and endures media temperatures up to 750°F, giving operators confidence in both safety and performance. Features 3-A" Tri-Clamp® Sanitary Connection 0.5% Accuracy (3/4" Tri-Clamp® +/- 1.0%) Display and Electrical Connection are Independently Rotatable 335 ° /343 ° Zero & Span Adjustment Designed for "Clean-in-place" and "Sterilize-in-place" 316 Stainless Wetted Parts Media Temperature Up to 750 ° F Excellent Long-term Stability Specifications Brand: ReoTemp Series: TSTDS Output Signal: 4-20mA, 3-wire (standard), 0-5V, 0-10V, 1-6V (3-wire), Switchable from 4-20mA to 0-10 VDC Measuring Principle: Thin-film-on-steel Pressure Ranges: Vacuum, Compound, Pressure to 7,500psi Accuracy NLH at 77 ° F (BSL): ±0.25% of span, ±1.0% of span with 3/4" Tri-Clamp Input: 15-30 Vdc (4-20mA), 15-30 Vdc (0-5V, 1-6V), 15-30 Vdc (0-10V) Temperature: Temperature effect with 1.5" or 2" Tri-Clamp®: ±0.1% of span/10 ° F (for zero and span) or ±0.02 psi/10 ° F (greater of). Note: 3/4" Tri-Clamp® not recommended for temperature variations. Effect is less than or equal too ±0.9 psi/10 ° F, Media: -13 to 185 ° F, Ambient: -13 to 185 ° FEnvironmental Rating: IP67 Switching Output: 2 Transistors PNP Pressure Unit for Display: PSI, Bar, MPa, kPa, mWC, mmWC, %, User Scale Downloads Instructions (PDF Download) Specifications Sheet (PDF Download) - TEST
This is your item. Ready to proceed?
Add it to your RFQ basket or submit your requirement directly — ACG will respond within 24 hours with pricing, availability and delivery options.